Failure And Replacement Of Components Of The Distributed I/Os - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

Failure and replacement of components during redundant operation

11.2 Failure and replacement of components of the distributed I/Os

11.2
Failure and replacement of components of the distributed I/Os
Which components can be replaced?
The following components of the distributed I/Os can be replaced during operation:
● PROFIBUS DP master
● PROFIBUS DP interface module (IM 153-2 or IM 157)
● PROFIBUS DP slave
● PROFIBUS DP cable
● Input/output or function modules in a distributed station
Replacement of signal and function modules
Note the different procedures.
Minor injury or damage to equipment is possible.
The procedure for replacing and input/output or function module differs for modules of the
S7-300 and S7-400.
Use the correct procedure when replacing a module. The correct procedure is described
below for the S7-400 in Chapter Failure and replacement of an input/output or function
module (Page 188).
To replace signal and function modules of an S7-300, perform the following steps:
Step
What to do?
1
Disconnect the module from its load current supply.
2
Remove the failed module (in RUN mode).
3
Disconnect the front connector and wiring.
4
Plug the front connector into the new module.
5
Insert the new module.
194
CAUTION
How does the system react?
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
-
-
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
Parameters are assigned automatically to the
module by the CPU concerned and the module is
addressed again.
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB