Siemens SIMATIC PCS 7 CPU 410-5H System Manual page 119

Process control system / process automation
Table of Contents

Advertisement

Influencing the cyclic self-test
SFC 90 "H_CTRL" allows you to influence the scope and execution of the cyclic self-test. For
example, you can remove various test components from the overall test and re-introduce
them. In addition, you can explicitly call and process specific test components.
For detailed information on SFC 90 "H_CTRL", refer to Manual
S7-300/400, System and Standard Functions
Note
In a fail-safe system, you are not allowed to disable and then re-enable the cyclic self-tests.
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
Operator controls and operating modes of the CPU 410-5H
.
7.3 Self-test
System Software for
119