INSTALLATION

7 UNPACKING THE PRODUCT

R
7200/3F HV PLUS solar heaters are supplied in a single pack-
age on a wooden pallet.
The insulation and cladding components on models 2000 and
3000 are supplied separately from the structural parts and should
be assembled when you receive the product, as described in the
section "Fitting the insulation (models 2000 - 3000)".
The following items are delivered in a plastic bag inside the
packaging:
− Instruction manual
− Bar code labels
− Hydraulic test certificate
9
The instruction manual is an integral part of the solar stor-
age cylinder. Once located, read it thoroughly and keep it
safe.
9
For handling operations, thoroughly follow the instructions
on device package label.

8 INSTALLING THE MAGNESIUM ANODES

Use the anodes provided; when assembling, note the position
and lengths provided in the technical data table.
7200/3F HV PLUS 800 ÷ 1500 models
− Partially remove the cladding, remove the washer and
unscrew the anode-holder plug in the sleeve using a
spanner
− Insert the anode provided, tighten the anode using a
spanner and then put the washer back in position.
7200/3F HV PLUS 2000 - 3000 models
− Before fitting the cladding, unscrew the anode-holder
plug in the sleeve using a spanner
− Insert the anode provided and tighten the anode using
a spanner.
NOTE: Tighten the anode plug to a torque of 25-30 Nm.

9 FITTING THE INSULATION (MODELS 2000 - 3000)

Once the tank is in the right position in the installation room,
the insulation and finishing parts for the tank can be installed.
Proceed as follows:
− Wrap the insulation (1) around the storage cylinder, care-
fully lining up the fittings with the holes on the inside
of the insulation. Secure the insulation in place with the
zips (2) at the edges of the two sections
2
1
− Drill the holes in the insulation for the connectors and
insert the washers (3)
− Fit the flange cover (4)
− Finally, fit the insulation top panel (5) and cover it with
the thermoformed cover (6).