Carrier 40KMC Series Installation Instructions Manual page 9

In-ceiling cassette duct - free split system, sizes 018 to 036
Hide thumbs Also See for 40KMC Series:
Table of Contents

Advertisement

38QRF
Units
1. Assemble
the connector
tubes to the factory
supplied
filter
drier by brazing
the factory supplied
flare connectors
to the
inlet and outlet for the filter drier (see Fig. 16)
BODY
A09507
Fig. 16 - 38QRF018-036
Connector
Tube Assembly
2. Perform
step 2 and 3 from the 38HDF
section.
3. Remove
the plastic
cap from the liquid
and suction
service
valve
on the 38QRF
unit and assemble
the heating
piston
and piston
cap supplied
with
the outdoor
unit as shown
in
Fig. 17.
--P ISTON
HEAT IN6
PISTON CAP
TOR
L/
]
METEREDFLOW
J
"=HEATING
Fig. 17 - AccuRater
(bypass
type)
Metering
Device
Components
Heat Pump
Systems
Only
A07407
NOTE:
The Teflon seal on the piston
should
point
towards
the
liquid
service
valve.
The
size of the
factory
supplied
piston
might
have to be adjusted
for long line applications
(over 80 ft
/ 24.4 m). Refer
to the Duct
Free Long
Line Application
Guide
for additional
information.
4. Attach the flare end of the filter drier assembly
to the piston
cap (see Fig. 17).
5. Connect
the field
supplied
line
set to the filter
drier
as-
sembly
and to the suction
valve.
6. Insulate
any exposed
areas between
filter drier
and liquid
valve.
Complete
Outdoor
Power
and Control
Wiring
ELECTRICAL
SHOCK
HAZARD
Failure to follow
this warning
could result in personal
injury or
death.
The
unit
cabinet
must
have
an uninterrupted
or unbroken
ground
to minimize
personal
injury if an electrical
fault should
occur.
The
ground
may
consist
of electrical
wire
or metal
conduit
when
installed
in accordance
with
existing
electrical
codes.
UNIT
DAMAGE
HAZARD
Failure to follow
this caution
may result in equipment
damage
or improper
operation.
Unit failure as a result of operation
on improper
line voltage
or
excessive
phase
imbalance
constitutes
abuse
and may
cause
damage
to electrical
components.
Such
operation
could
void
any applicable
Carrier warranty.
ELECTRICAL
SHOCK
HAZARD
Failure
to follow
this warning
could
result in personal
iniury
or death.
Before
performing
service
or maintenance,
be sure indoor
unit main power switch
is turned
OFF and indoor
blower
has
stopped.
Lock out and tag switch with a suitable warning
label.
Power
Wiring
1. Mount outdoor power disconnect. The unit is factory wired
for the voltage shown on the unit nameplate. The fused dis-
connect switch nmst be provided within sight of the unit,
readily accessible, but out of reach of children. Provisions
for locking the disconnect switch on the OFF (open) posi-
tion is advisable. The disconnect switch must comply with
NEC and local codes, Protect the unit and wiring using
only the recommended
fuse/circuit
breaker
size. See
Table 8.
2. Run power wiring from main box to disconnect per NEC
and local codes.
3. Run power wiring from the disconnect switch to outdoor
unit. Use only minimum 60°C copper conductors between
the disconnect switch and the unit for field power connec-
tion,
4. Route the field power wires through the conduit connection
opening in the unit side panel and connect in junction box
as shown in Fig 18. The unit and power wiring must be
grounded,
TO--"
_-----
BLK
NGLE-PHAS7
THREE-PHASE
CONNTO
DISCONNECT
PER NEC
=GROUND
LEAD,
LEGEND
NEC -- National
Electrical
Code
-- Splice
(field)
-- --
' Field Wiring
Factory
Wiring
=d_
BLK
=_i
BLU --
=_::_-
YEL
._]
GROUNDING
LUG
THREE-PHASE
UNIT
Fig. 18 - Line Power
Connections
A08251
NOTE:
Operating
unit
on improper
line
voltage
constitutes
abuse
and
may affect
Carrier
warranty.
DO NOT
install
unit
in
a
system
where
voltage
may
fluctuate
above
or
below
permissible
limits.
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents