Carrier 40KMC Series Installation Instructions Manual page 18

In-ceiling cassette duct - free split system, sizes 018 to 036
Hide thumbs Also See for 40KMC Series:
Table of Contents

Advertisement

7. Connect
L1 to the black wire and L2 to the red wire using
wire nuts and fix the ground
wire between
the two washers.
The internal
control
panel can be accessed
by opening
the grille
and removing
the metal cover attached
by four screws.
NOTE:
The internal
control
panel
does not need to be accessed
during
the installation
process
unless
there is a need for service.
8. If any accessories
are being installed,
refer to the individual
accessory
instructions
for guidance
on wire
routing
at this
time.
Install
All
Power_ Interconnecting
Wiring_ Piping
and
Drain
Hose
to Indoor
Unit.
1. Run control wiring
from the outdoor
unit through the access
hole in the wall and make
sure you have
enough
wire to
reach the control box of the unit once hung on the mounting
plate.
2. Complete
refrigerant
piping
connections.
a. cut the extreme
end of the tubes and remove
any copper
shavings
with a de-burring
blade.
b. Remove
the flare nut from the "Flare"
connection
body
of the indoor
unit and insert them into the pipes.
c. make the flares to the pipe ends with the proper flaring
too. The flare end nmst not have any burrs or imperfec-
tions,
the flared walls must be uniform.
See Fig. 26
and Fig. 27.
Fig. 26 - Removing
Burrs
I
I
i
I
I
I
I
i
I
I
I
Fig. 27 - Flared
Walls are Equal
A07199
A07200
d. Lubricate
the end of the pipe and thread
of the flare
connection
with refrigerant
oil. Tighten
by hand
and
then use two wrenches
(see Fig. 28) to tighten
all con-
nections
fully applying
the tightening
torque shown
in
Table 13.
@ Outdoor end
n or _orque wrench
-_\
&...._
@ Indoor end
_ \
"-/
A07201
Fig. 28 - Tightening
Connections
Table 13 -TighteningTorque
TUBE DIAMETER (in.)
TORQUE
fft.-Ib)
3/8 in.
31
5/8 in.
48
3/4 in.
74
3,
_)
(f)
Indoor unit piping
@
Connection
w_ring
@ Drain hose
_--_
r _f_
J
Fig. 29 - Location
of Piping,
Hose,
and Wiring
A08364
Connect
condensate
drain piping
Observe
all local sanitary
codes when installing
condensate
drains.
The condensate
may be discharged
at a maximum
height
of 7-1/8
in, (181 ram) above the unit as long
as the
ascending
tube is vertical
and aligned
with drainage
flange.
If it is necessary
to discharge
the condensate
from
a level
above
7-1/8
in. (181
ram), install
an auxiliary
water
dis-
charge pump and a float valve.
A float valve
is recommen-
ded to stop the compressor
if there is a fault at the auxiliary
pump.
18