Carrier 40KMC Series Installation Instructions Manual page 19

In-ceiling cassette duct - free split system, sizes 018 to 036
Hide thumbs Also See for 40KMC Series:
Table of Contents

Advertisement

a.Use hard p olyvinyl chloride (PVC) pipe material with
nominal IDof1in.toconnect atdrain l ine.Toensure
correct condensate
water flow, the pipe s hould have a
gradient of2% without obstruction.
See F ig. 3 0
PERSONAL
INJURY
HAZARD
Failure
to follow
this caution
may result in personal
injury.
The
drain
tube
extension
must
be securely
fastened
to the
condensate
drain.
Failure
to do so could
result in condensate
water dripping
on to the floor.
b. A trap of at least 2 in. (51 mm) in depth should be made
to prevent
unpleasant
odors
from reaching
the room.
c. Insulate
condensate
pipe with condensation
proof mater-
ial such as polyurethane,
propylene,
or neoprene
of 3/16
in. to 3/8 in. thickness.
4. Complete
Control
Wiring
a. Route the control
wiring
through
the 7/8 in. knockouts
on the left or right hand side of the external
control
box
(low voltage
side).
b. Connect
R and Y wires to the terminal
block for cooling
only units (40KMC)
and heat pump units (40KMQ)
that
are matched
with the 38HDF
outdoor
units. See Fig. 24.
c. Connect
the R, Y, O, G, DT, A, and B wires to the
(PGB-1)
1 terminal
on the 40KMQ
heat pump indoor
units.
See Fig. 25.
5. Perform
any modifications
required
for the accessory
user
interface.
Three types of user interface
can be used with the
unit: Wall mounted
wired
control,
Wireless
remote
control
and Zone Manager.
a. Wall Mounted
Remote
Control
The unit comes ready from the factory for use with a
wall mounted
wired control.
Refer to the installation
instructions
of the wired remote
control for additional
information.
The wall mounted
wired control
connects
to terminals
P, G, and C located
in the external
control
box.
See Fig. 24 and Fig. 25. If there is a desire to
control
multiple
units (up to 6) from one wired
remote
control,
the units should be wired as shown
in Fig. 31.
Fig. 30 - Condensate
Drain
Pipe
A07191
UNIT1
UNIT
5
(9
J
UNIT
3 ---
__J5
(9
(9
®
*@
!
UP TO 6 UNITS
A
- MAIN
BOARD
(9
" WIRING
KIT 33MC9005
(9
" BLACK
(9
" RED
(9
- WHITE
* 100 ohm Resistor
Fig. 31 - Multiple
Unit
Control
Wiring
A09513
19