Carrier 40KMC Series Installation Instructions Manual page 24

In-ceiling cassette duct - free split system, sizes 018 to 036
Hide thumbs Also See for 40KMC Series:
Table of Contents

Advertisement

START-UP
Preliminary
Checks
1. Make
sure all wiring
connections
are correct
and they are
tight.
2. Field
electrical
power
source
must
agree
with
unit name
plate rating.
3. Check
that all barriers,
covers,
and panels
are in place. En-
sure that the filters
and return-air
grilles
on the indoor
unit
have been installed
and that the discharge
louvers
are posi-
tioned
correctly.
4. All service valves must be closed.
5. On units with crankcase
heaters,
ensure
belly-band
heaters
are tight around
the compressor.
Evacuate
and Dehydrate
the System
[]NIT DAMAGE
HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant
tubes
and indoor
coil should
be evacuated
using
the
recommended
deep vacuum
method
of 500 nficrons,
the alternate
triple evacuation
method
may be used
if the procedure
outlined
below is followed.
Always
break
a vacuum
with dry nitrogen.
[]sing Vacuum
Pump
1. Completely
tighten
flare nuts A, B, C, D, connect
manifold
gage charge
hose to a charge
port of the low side service
valve.
(See Fig. 40.)
2. Connect
charge hose to vacuum
pump.
3. Fully open the low side of manifold
gage. (See Fig. 41)
4. Start vacuum
pump
5. Evacuate
using
either
deep
vacuum
or triple
evacuation
method.
6. After
evacuation
is complete,
fully
close
the low
side of
manifold
gage and stop operation
of vacuum
pump.
7. The factory
charge contained
in the outdoor
unit is good for
up to 25 ft. (8 m) of line length.
For refrigerant
lines longer
than 25 ft (8 m), add 0.3 oz. per foot of extra piping
up to
the maximum
allowable
length.
8. Disconnect
charge hose from charge
connection
of the low
side service valve.
9. Fully open service valves B and A.
10. Securely
tighten
caps of service valves.
Outdoor Unit
Refrigerant
_B
Low Side
High Side
Service
Valve
Indoor Unit
A07360
Fig. 40 - Service
Valve
Manifold Gage
500 microns
_
low
side valve
..-'," _ L_
High side valve
Charge
hose--_
_,d
Charge
hose
[_4
__//Vacuum
pump
//
\
Low side valve
Fig. 41 - Manifold
A07361
Deep Vacuum
Method
The
deep
vacuum
method
requires
a vacuum
pump
capable
of
pulling
a vacuum
of 500 nficrons
and a vacuum
gage
capable
of
accurately
measuring
this vacuum
depth. The deep vacuum
method
is the most
liquid
water.
if)
Z
O
iv-
O
m
_ositive
way of assuring
a system
is free of air and
See Fig. 42)
LEAK IN
SYSTEM
.VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
1
2
3
4
5
6
7
MINUTES
Fig. 42 - Deep Vacuum
Graph
A95424
Triple
Evacuation
Method
The triple evacuation
method
should
only
be used when vacuum
pump
is only
capable
of pumping
down
to 28 in. of mercury
vacuum
and system does not contain
any liquid water.
Refer to Fig. 43 and proceed
as follows:
1. Pump system
down
to 28 in. of mercury
and allow pump to
continue
operating
for an additional
15 nfinutes.
2. Close service valves
and shut off vacuum
pump.
3. Connect
a nitrogen
cylinder
and regulator
to system
and
open until system
pressure
is 2 psig.
4. Close service valve and allow system
to stand for 1 hr. Dur-
ing this time, dry nitrogen
will be aMe to diffuse throughout
the system
absorbing
moisture.
5. Repeat
this procedure
as indicated
in Fig. 43. System
will
then be
free of any contanfinants
and water vapor.
24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents