Carrier 40KMC Series Installation Instructions Manual page 27

In-ceiling cassette duct - free split system, sizes 018 to 036
Hide thumbs Also See for 40KMC Series:
Table of Contents

Advertisement

PROBLEM
Compressor
and Fan of the Outdoor
Unit Will Not Start
Compressor
Will Not Start, But Out-
door Fan is Operating
Compressor
Stops Due to Over-tem-
perature
Compressor
Runs Continuously
Frequent Ice-Build-Up
on Outdoor
Coil
Discharge Pressure Too High
Discharge Pressure Too Low
Suction Pressure
Too High
Suction Pressure
Too Low
Outdoor
Fan Cycling
Due to Over-
Temperature
Protection
Table
15 - Troubleshooting
POSSIBLE CAUSE
Unit not energized
Main switch is set to OFF
Main switch fuses are blown
Compressor
cycling protection
is on
Main power voltage is too low
Electrical connections
are too loose or are wrong
Electrical connections
of compressor
are loose or
wrong
Compressor
burnt out; seized or protection
device
on
Wrong refrigerant
charge in unit (excessive or low)
or air or other non-condensable
gasses in the
circuit
Main voltage
is too high or too low
Condenser
coil obstructed
Outdoor fan off
Wrong indoor unit thermistors
Refrigerant
circuit clogged
Reversing valve faulty on heat pump models
Expansion device clogged or covered with ice
Unit selected is too small for application
require-
ments
Indoor temperature
setting too low or too high
Outdoor
unit fan faulty
Air or other non-condensable
gasses in the cir-
cuit
Obstructions
at air intake or dirty indoor unit filters
Outdoor fan is stopped
Outdoor
coil dirty or obstructed
Condenser
fan faulty
Indoor temperature
setting too low or too high
Air or other non-condensable
gasses in the cir-
cuit
Indoor temperature
setting too high or too low
Outdoor
coil dirty or obstructed
Indoor unit air filter dirty
Indoor temperature
setting too high or too low
Reversing valve faulty or internal leak
Indoor temperature
setting too high or too low
Evaporator
coil covered with ice
Expansion device or suction line clogged
Outdoor fan does not stop during defrost periods
Electrical connection
loose
Fan motor burn out
Fan bearing seized
Expansion device clogged or covered with ice
SOLUTION
Check the main power connection.
Check and put it to ON position.
Replace fuses.
Wait for 3 minutes.
Check and set to the correct voltage.
Check and tighten or correct connections.
Check and tighten or repair compressor.
Check for the cause and replace compressor
if neces-
sary.
Drain refrigerant,
evacuate and recharge.
CAUTION:
Do not vent refrigerant to the atmosphere;
use
refrigerant
recovery equipment.
Check voltage setting and adjust if necessary.
Remove obstruction.
Check cause and resume operation
or repair.
Replace thermistors.
Check and remove obstructions.
Replace reversing
valve.
Drain refrigerant,
evacuate and recharge.
CAUTION:
Do not vent refrigerant to the atmosphere;
use
refrigerant
recovery equipment.
Contact a qualified service technician
for a system evalu-
ation.
Check temperature
setting.
Replace outdoor
fan.
Drain refrigerant,
evacuate and recharge.
CAUTION:
Do not vent refrigerant to the atmosphere;
use
refrigerant
recovery equipment.
Remove obstruction
and/or clean filter.
Check cause and repair.
Clean or remove obstructions.
Replace condenser
fan.
Check temperature
setting.
Drain refrigerant,
evacuate and recharge.
CAUTION:
Do not vent refrigerant to the atmosphere;
use
refrigerant
recovery equipment.
Check temperature
setting.
Clean or remove obstructions.
Clean filter.
Check temperature
setting.
Replace reversing
valve.
Check temperature
setting.
Air circulation
on the evaporator
not sufficient; check and
repair.
Check and repair.
Check electrical
parts.
Check connections.
Replace.
Check and repair.
Drain refrigerant,
evacuate and replace.
CAUTION:
Do not vent refrigerant to the atmosphere;
use
refrigerant
recovery equipment.
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents