Venting System Assembly

General Information
The Stardance is approved for installation only with the
vent components listed on Pages 12 & 13. Follow the
vent component instructions exactly.
For U.S. installations: The venting system must con-
form with local codes and/or the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54
For Canadian installations: The venting system must
conform to the current CSA B149.1 installation code.

Rear Vent

Use Rear Vent Kit 7TFSRSK for an installation where
the heater is parallel to the wall and the vent system
extends straight back through that wall.
1. Attach Inner Starter Pipe, (found in with the logset),
to the stove.
Run a bead of sealant beneath the pipe bead and
attach to the stove using three 1/4-20 x 3/8" phillips
screws provided in the parts bag. (Fig. 17)
Sealant
Phillips
Screws
Fig. 17 Apply sealant to the starter pipe, and fasten to stove
with Phillips screws.
20012950
Rheostat
FK104
ST347a
JUV
FK28
rheostat install
9/21/00
ST937
�����
��������� ��
������� ����
����
Stardance Direct Vent - Rear Vent Gas Heaters
2. Locate the vent opening on the wall. Refer to Fig-
ures 18 & 19 to determine the top of the opening
centerline. It may be necessary to first position the
stove and measure to find the hole location. De-
pending on whether the wall is made of combustible
materials, cut the opening to the size shown in Fig-
ure 18. Combustible wall openings must be framed
as shown in Figure 18.
Vent Opening - Combustible Wall
9³⁄₈"
(240mm)
9³⁄₈"
(240mm)
Vent Opening -Noncombustible Wall
7¹⁄₂"
(191mm)
Fig. 18 Locate vent opening.
3. Measure the wall thickness and cut the wall sleeve
sections to proper length (MAXIMUM 12"). Assemble
the sleeve with the #8 sheet metal screws supplied.
Attach the firestop plate to the sleeve end with the
holes. (Fig. 24) NOTE: The wall sleeve is required in
VO584-100
combustible walls only.
4. Install the Wall Firestop/Sleeve assembly into the
Vent Opening
wall cutout and fasten the firestop to the wall cutout
2/99 djt
framing members. (Figs. 19)
5. Measure, and cut if necessary, the appropriate
length of pipe section needed to make the connec-
tion through the wall.
9³⁄₈" W x 10³⁄₈" H
Wall Opening
Wall Sleeve
- Seal Around
C L
27���"
(695mm)
to Top of
Opening
Seal
22���"
Around
(565 mm)
Terminal
ST477
Fig. 19 Rear Vent Kit 7TFSRSK installation.
ST477
rear vent kit
6/00
Framing Detail
VO584-100
Firestop
Ventilated Wall Plate
- Open End Down
Finishing Collar
15