Zones Test; Figure 11: Zone Test Menu 1; Figure 12: Zone Test Menu 2; Figure 13: Zone Test Menu 3 - Bosch Radionics D8024 Operator's Manual

Analog fire alarm control panel
Hide thumbs Also See for Radionics D8024:
Table of Contents

Advertisement

D8024
Control Level 2

4.4.1.3 Zones Test

Press the [3] key to select Zones. The Zones Test allows the operator to test devices on the polling circuit(s) and
peripheral device circuit(s) without having to reset the panel after each device is tested.
Note:
If no action is taken within one minute, the display reverts to the normal display. Press the [>] key to restore the Test
display.
The panel displays Zone Test Menu 1.
Press the [Yes] key to activate the NAC devices briefly as each device is tested, or press the [No] key to bypass the
indicator test. The panel then displays Zone Test Menu 2.
Enter the number of the first zone to be tested and press [Enter]. The panel will then display Zone Test Menu 3. If, for
example, "12" is keyed in, the display would show:
If "15" is keyed in, the panel would display the Walk Test Mode as follows:
The moving "W" across the lower line alternates with a "Press NO to EXIT" message.
Note:
Once the display indicates the panel is in the Walk Test Mode, the display will not revert to normal. The panel will
terminate the test and sound the panel buzzer if there is no activity for a 20 minute period.
The operator may test devices within the zone parameters shown on the display. The panel responds to each test by:
• Displaying an activation message on the alphanumeric display
• Entering the activation in the event log
• Lighting the alarm LED in the Zone/Area display
• Sounding the panel buzzer
• Lighting the LED at the device in alarm
After a few seconds, the panel will automatically reset and turn off the device LED. The panel allows up to one minute for
smoke detectors to clear. The operator may then test the next device.
Note:
If the panel detects an alarm condition in a zone other than those being tested, all NAC devices and relays will activate
as programmed. NAC devices will continue to operate until silenced from the panel.
Terminate the Walk Test by pressing the [No] key. The display will return to the Main Menu (see Figure 9).
Note:
The fourth option on the Test Menu, 4) Outputs, is not available to Control Level 2 operators.
35394D
Ring bells?

Figure 11: Zone Test Menu 1

Test from zone?
(key in number, then press "Enter')

Figure 12: Zone Test Menu 2

Test from 12 to zone ?
(key in number, then press "Enter")

Figure 13: Zone Test Menu 3

Test from 12 to Zone 15
----------W----------

Figure 14: Zone Test Menu 4

D8024 Operator's Guide
Page 16