Replacing The Power Stack Adapter - Siemens SINAMICS SM150 Operating Instructions Manual

Medium-voltage drive
Table of Contents

Advertisement

Note
Venting the phase module
It is not necessary to vent the phase module.
Check the water level in the expansion vessel of the re-cooling unit. If necessary, add water.
For more detailed information, refer to the operating instructions of the re-cooling unit.
9.5.6

Replacing the Power Stack Adapter

Required tools
● Torx screwdriver Tx30
● 2.5 mm slotted screwdriver
Removing the Power Stack Adapter
1. Withdraw all fiber-optic cables
2. Withdraw all DRIVE-CLiQ cables directly at the connectors.
3. Use a slotted screwdriver to remove the connectors for the control cables.
4. Remove the ground connection on the Power Stack Adapter chassis.
5. Use a Torx screwdriver to loosen the four fastening screws of the Power Stack Adapter. Do
6. Push the Power Stack Adapter upwards.
7. Remove the Power Stack Adapter.
SINAMICS SM150 6SL3845-7NN42-2AA3 HBIS Shigang WRM NTM
Operating Instructions Rev.202003051222 3005356504
Ensure that the disconnection is made only directly on the connector and not on the fiber-
optic cable.
Disconnect the connectors for the control cables from the terminal strip.
not remove the screws.
Maintenance
9.5 Repair
147