Depending on the drive transformer version (dry or oil filled), inte‐
grate the transformer protection and monitoring devices in the alarm
and shutdown train of the drive. A range of digital inputs are available
for this purpose on the customer terminal strip.
Options L80 to L82
The PTC thermistor sensors (type A PTC resistors) must be connec‐
ted to the thermistor motor protection unit ‑F at terminals T1 and T2
for alarm/shutdown purposes.
Options L91; L93, 94, 95, 96
The resistance thermometers must be connected to evaluation unit
‑A1 to evaluate the PT100. The two-wire or three-wire system can be
used here to connect the PT100 sensors. The sensors are divided
into two groups. This must be taken into account when the evaluation
is performed (factory setting).
To check the correct wiring and macro interconnection, first select
limits below the ambient temperature and check the messages.
After checking the correct wiring and macro interconnection, set the
limit values for alarm and shutdown to match the component moni‐
tored.
Differential pressure monitoring
Check the entry for parameter p0263. The setting
must not exceed 3 seconds.
1. In the infeed, select "Test operation cooling" (infeed p6650).
2. Switch on test operation via infeed p6651.
3. In the cooling system, close the main valve for the cooling water
4. Reopen the valve.
5. Acknowledge the fault and switch test operation off again.
Option K50
If a function for detecting the actual speed value is provided to im‐
prove speed accuracy, connect the motor rotary pulse encoder to the
SMC30 ( A... ).
Option L32
If, for process-related reasons, the drive needs to be restarted after
power failures of > 100 ms, connect the synchronization voltage of
the line upstream of the medium-voltage circuit-breaker to the VSM
10. To do so, install voltage transformers at the medium-voltage lev‐
el, which supply 3-phase 100 V AC as the synchronization voltage.
Connect the voltage transformers on the drive side to terminals.
SINAMICS SM150 6SL3845-7NN42-2AA3 HBIS Shigang WRM NTM
Operating Instructions Rev.202003051222 3005356504
feed to the drive. The drive must switch off with the following fault:
"F49158 cooling system: Differential pressure has fallen below
the fault threshold".
( P6651 = 0, P6650 = 0 )
C.2 Checklist for electrical installation
Connecting Sensor Modules
Checklists and forms
Available
/completed
163