Parker EME
3.5

Signal interfaces

3.5.1.

RS232 / RS485 interface (plug X10)

Note on Compax3H
In this chapter you can read about:
RS232 / RS485 interface (plug X10) ................................................................................ 31
Resolver / Feedback (connector X13) .............................................................................. 32
Analogue / encoder (plug X11) ........................................................................................ 34
Digital inputs/outputs (plug X12) ...................................................................................... 35
Optional input/output cards .............................................................................................. 36
Interface selectable by contact functions assignment of X10/1:
X10/1=0V RS232
X10/1=5V RS485
PIN X10
RS232 (Sub D)
1
(Enable RS232) 0V
2
RxD
3
TxD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
+5V
RS485 two wire (Sub D)
PIN X10
Pin 1 and 9 jumpered externally
1
Enable RS485 (+5V)
2
res.
3
TxD_RxD/
4
res.
5
GND
6
res.
7
TxD_RxD
8
res.
9
+5V
RS485 four wire (Sub D)
PIN X10
Pin 1 and 9 externally jumpered
1
Enable RS485 (+5V)
2
RxD
3
TxD/
4
res.
5
GND
6
res.
7
TxD
8
RxD/
9
+5V
USB - RS232/RS485 converter
The following USB - RS232 converters were tested:
ATEN UC 232A
USB GMUS-03 (available under several company names)
USB / RS485: Moxa Uport 1130
http://www.moxa.com/product/UPort_1130_1130I.htm
Ethernet/RS232/RS485: NetCom 113 http://www.vscom.de/666.htm
Exsys Adapter USB to RS232 with FTDI processor (Windows 7)
If X10 at the control unit is used, the programming interface as well as the
external device status LEDs are out of order due to the removal of the X10
192-120102 N19 June 2014
jumper (VBK17/01)!