Siemens SINAMICS S120 Manual page 44

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Mechanical installation
3.1 Important notes
Note
Notes regarding transportation
• The devices are packaged by the manufacturer in accordance with the climatic conditions
and stress encountered during transit and in the recipient country.
• The notes on the packaging relating to transportation, storage, and proper handling must
be observed.
• For transportation using forklifts, the devices must be set down on a wooden pallet.
• When the devices are unpacked, they can be transported using the optional transport
eyebolts (option M90) or rails on the cabinet unit. The load must be distributed evenly.
Heavy blows or impacts must be avoided during transit and when the devices are being
set down, for example.
• Shock/tilt indicators are affixed to the packaging to detect unacceptable impact or tilting of
the cabinet unit during transport (see Chapter Shipping and handling indicators
(Page 50)).
• Permissible ambient temperatures:
Air cooling: -25 to +70 °C, Class 2K3 acc. to IEC 60721-3-2
Briefly up to -40 °C for max. 24 hours
Note
Notes regarding damage in transit
• Carry out a thorough visual inspection of the device before accepting the delivery from
the transportation company. Pay special attention to transport damage that is not readily
apparent but indicated by the tilt and shock indicators.
• Check that you have received all the items specified on the delivery note.
• Notify the shipping company immediately of any missing components or damage.
• If you identify any hidden defects or damage, contact the transportation company
immediately and ask them to examine the device.
• If you fail to contact them immediately, you may lose your right to claim compensation for
the defects and damage.
• If necessary, you can request the support of your local Siemens office.
Storage
The cabinet units must be stored in clean, dry rooms. Temperatures between -25° C and
+55° C are permissible (class 1K4 acc. to EN 60721-3-1). Temperature variations greater
than 20 K per hour are not permitted.
If the cabinets are stored for a prolonged period, cover them or take other appropriate
measures to ensure that they do not become dirty and that they are protected against
environmental influences. If such measures are not taken, the warranty becomes invalid in
the event of a claim for damages.
44
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A

Advertisement

Table of Contents
loading

Table of Contents