Cabinet Modules
6.4 Heat Exchanger Modules
Damage to the flexible pipe is incorrectly routed
The flexible pipe can be damaged due to mechanical stress if incorrectly routed.
• Fix the flexible pipe so that it is not subject to any mechanical stress.
• Route the flexible pipe so that it does not touch the base plate, as otherwise it could be
6.4.3.3
Connection of the plant-side raw water circuit
The plant-side raw water circuit is connected at the pipe ends of the Heat Exchanger
Module.
Establishing the connection
Connection with the cooling connection at the Heat Exchanger Module:
1. For this connection use a connecting pipe and a pipe coupling with the appropriate
diameter.
Data is provided under Technical data.
2. Attach the pipe couplings corresponding to the manufacturers data.
198
CAUTION
mechanically damaged in operation due to vibration.
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A