Siemens SINAMICS S120 Manual page 303

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

S5: Selector for voltage/current AI0, AI1
Table 9- 10
Note
Delivery condition
When delivered, both switches are set to current measurement (switch set to "I").
X522: 2 analog outputs, temperature sensor connection
Table 9- 11
AO xV: analog output voltage; AO xC: Analog output current
1)
Max. connectable cross-section: 1.5 mm²
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Selector for voltage/current S5
Switch
S5.0
Selector voltage (V) / current (I) Al0
S5.1
Selector voltage (V) / current (I) Al1
Terminal block X522
Terminal
Designation
1
AO 0V+
2
AO 0-
3
AO 0C+
4
AO 1V+
5
AO 1-
6
AO 1C+
7
+Temp
8
-Temp
9.6 G60, Terminal Module TM31
Function
Technical data
1)
You can set the following output signals using pa-
rameters:
Voltage: -10 ... +10 V (max. 3 mA)
Current 1: 4 ... 20 mA (max. load resistance
≤ 500 Ω)
Current 2: -20 ... +20 mA (max. load resistance
≤ 500 Ω)
Current 3: 0 ... 20 mA (max. load resistance
≤ 500 Ω)
Resolution: 11 bits + sign
Continuously short-circuit proof
Temperature sensor KTY84-1C130/PTC
Measuring current via temperature sensor connec-
tion: 2 mA
Options