Siemens SINAMICS S120 Manual page 375

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 9- 44
Max. pulse frequency when a dV/dt filter compact plus VPL is used for units with a rated pulse frequency of
2 kHz
Article No.
6SL3725-
1TE41-4AS3
Table 9- 45
Max. pulse frequency when a dV/dt filter compact plus VPL is used for units with a rated pulse frequency of
1.25 kHz
Article No.
6SL3725-
1TE36-1AA3
1TE37-5AA3
1TE38-4AA3
1TE41-0AA3
1TE41-2AA3
1TE41-4AA3
1TG34-7AA3
1TG35-8AA3
1TG37-4AA3
1TG38-0AA3
1TG38-1AA3
1TG41-0AA3
1TG41-3AA3
1TG41-6AA3
Commissioning
During commissioning, the dV/dt filter compact plus Voltage Peak Limiter must be logged on
using STARTER or via the AOP30 operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
Parameter p0230 is reset when the factory setting is established. The parameter has to be
reset when recommissioning.
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Unit rating [kW]
Output current for a
pulse frequency of 2 kHz [A]
Line voltage 380 ... 480 V 3 AC
(DC-link voltage 510 ... 720 VDC)
800
Unit rating [kW]
Output current for a
pulse frequency of 1.25 kHz
Line voltage 380 ... 480 V 3 AC
(DC-link voltage 510 ... 720 VDC)
315
400
450
560
710
800
Line voltage 500 ... 690 V 3 AC
(DC-link voltage 675 ... 1035 VDC)
450
560
710
800
800
1000
1200
1500
9.23 L07, dV/dt filter compact plus Voltage Peak Limiter
Max. pulse frequency when a dV/dt filter is
1330
Max. pulse frequency when a dV/dt filter is
[A]
605
745
840
985
1260
1405
465
575
735
810
810
1025
1270
1560
Options
used
4 kHz
used
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
375