9.36 M06, base 100 mm high, RAL 7022

9.36
M06, base 100 mm high, RAL 7022
Availability of option
This option is available for the following S120 Cabinet Modules:
● Basic Line Connection Modules
● Active Line Connection Modules
● Motor Modules
● Heat Exchanger Module
Description
Because it is raised 100 mm, the supplementary cabinet base facilitates higher cable
bending radii (cable is fed in from below) and cable routing within the cabinet base.
The cabinet base comes completely assembled and is usually color RAL 7022.
Table 9- 59
Components of the cabinet base
Component
1 x base element (rear)
1 x base element (front)
Base covers 

(option M26/M27 only)
4 x cover caps
Connection to the foundation
To connect the cable marshalling compartment to the foundation, four holes for M12 screws
are provided. These are in line with the holes in the cabinet. The fixing dimensions are
specified on the associated dimension drawings.
Connection for side-by-side installation of cabinet units
The individual bases are not connected for cabinet units installed in a side-by-side
configuration. The connection from the base to the cabinet and between the cabinet units
ensures sufficient stability.
Note
In transport units, the base covers inside the transport unit are only secured at the bottom
and are folded down parallel to the ground.
392
Connection element
Fixing elements
On the cabinet:
The cabinet base is shipped pre-assembled.
On the foundation:
The holes are in line with the holes in the
cabinet (see dimension drawings).
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A