Mains And Motor Terminals, Fsa; Mains And Motor Terminals, Fsd - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230, ip20 / push through
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Connecting
4.1 Mains and Motor Connection
4.1.3
Mains and Motor Terminals, FSA ... FSC
The figure shows the layout of mains and
motor terminals.
The Power Modules are fitted with two-part-
connectors. The removable part of the
connector can be unplugged from the power
module by pressing the release catch. The
connectors cannot be interchanged.
Tightening torques:
 FSA 0.4 Nm ... 0.5 Nm (4 lbf in)
 FSB 0.55 Nm ... 0.6 Nm (5 lbf in)
 FSC 1.2 Nm ... 1.5 Nm (11 ... 13 lbf in)
4.1.4
Mains and Motor Terminals, FSD ... FSF
Access to Power and Motor Terminals
To get access to the power and
motor terminals, adhere the
following steps:
1. Release the latch on each
2. Turn the terminal covers
Mains and Motor Terminals
The figure shows the layout of the
mains and motor terminals.
Tightening torques:
 FSD 6 Nm (53 lbf in)
 FSE 6 Nm (53 lbf in)
 FSF 13 Nm (115 lbf in)
26
side of the terminal covers
with a suitable flat-bladed
screwdriver
upwards and lock into
position
1
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
2

Advertisement

Table of Contents
loading

Table of Contents