Figure 4-3
Figure 4-4
Note
Connect a Power Module with integrated line filter with an unshielded cable to the mains
power.
If you use an external line filter, you will need a shielded cable between the line filter and the
Power Module.
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
Line supply connection
Motor connection
Power supply cable (unshielded)
Motor connection cable (shielded)
Cable shield
Cable clamps for a good conductive electrical connection through a large surface area between
the shield and mounting plate
EMC-compliant wiring - on the left without shield plate, on the right with shield plate
Shield connection - detail
Serrated collar
Cable tie
Metal mounting plate (unpainted and with a good
electrical conductivity)
Shield plate (option)
Connecting
4.2 EMC compliant connection