Permissible converter overload
The converters have different power ratings "High Overload" and "Low Overload" depending
on the expected load.
Figure 6-1
Note
Please note the base load (100 % power or current) for Low Overload is higher than the
base load for High Overload.
The load characteristics shown in the diagram are only examples. We recommend the use of
the "SIZER" engineering software to select the appropriate Power Modules using duty
cycles. See Sizer download
(http://support.automation.siemens.com/WW/view/en/10804987/130000).
Definitions
 LO input current
 LO output current 100 % of the permissible output current with a load cycle according to
 LO power
 HO input current
 HO output current 100 % of the permissible output current with a load cycle according to
 HO power
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
Duty cycles, "High Overload" and "Low Overload"
100 % of the permissible input current with a load cycle according to
Low Overload.
Low Overload.
Power of the Unit at LO output current.
100 % of the permissible input current with a load cycle according to
High Overload.
High Overload.
Power of the Unit at HO output current.
15
Technical specifications
43