Siemens SINAMICS G120P Hardware Installation Manual page 21

Power module pm230, ip20 / push through
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Table 3- 2
Dimensions
Frame Size
FSA filtered /unfiltered
FSB filtered /unfiltered
FSC filtered /unfiltered
Fixing:
FSA/FSB/FSC: Screws M5, 3 Nm
Using a screen termination kit:
1)
FSA: + 84 mm; FSB: + 85 mm; FSC: + 89 mm
plus 58 mm using a CU230, plus 40 mm using a CU240,
2)
plus another 10 mm or 25 mm using a BOP-2 or an IOP as Operator Panel (OP)
Distances
The Power Modules require a distance of 80 mm above and 100 mm below. They can be
mounted side-by-side. Due to tolerance reasons, we recommend a lateral distance of about
1 mm.
Mounting the shielding plate
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
Dimensions (mm)
Height
Width
Depth
1)
238
125.9
171
345
153.9
171
410,5
200
171
D1
D2
2)
117.7
53,1
117.7
53,1
117.7
53,1
Installing/Mounting
3.3 Mounting the Power Modules
a
b
c
103
106
88
147.5
134
116
123
174
156
d
e
198
27
304
34.5
365
30.5
21

Advertisement

Table of Contents
loading

Table of Contents