https://daikin-p.ru
3.3 Automatic PTI
● Automatic PTI enable condition
43 ℃ ≧ Ambient temperature ≧ -10.0 ℃
Ambient temperature above 43 ℃ or below -10.0 ℃ may result in PTI failure.
● Four options for automatic PTI are available, Short PTI, Full PTI, Chilled PTI and Frozen PTI.
PTI
Performed in order to find parts abnormalities. PTI continues even if abnormalities are
Short PTI
found during PTI. PTI terminate if controller detects a compressor failure or evaporator
fan is locked.
Short PTI, Chilled PTI and Frozen PTI are performed.
Full PTI
It terminates as soon as abnormalities are found after the completion of Short PTI
Short PTI and Chilled PTI are performed.
Chilled PTI
It terminates as soon as abnormalities are found after the completion of Short PTI
Short PTI and Frozen PTI are performed.
Frozen PTI
It terminates as soon as abnormalities are found after the completion of Short PTI
●Access
UNIT OFF
ON
Preparation for 10 sec.
System Check
10
Container ID
DILU1234567
Controller Date
DD/MM/ YYYY
Controller Time
17:00
Software Ver.
3031
※ Pass for completion of PTI operation for failure is displayed
1. Press MENU key at preparation display after I/O switch ON, and go to
"Initialize Menu".
2. Select "PTI Menu" and press
Menu".
3. Select PTI and press
4. Press I/O switch OFF when the PTI is completed.
Switch OFF
[ Initialize Menu ]
Initialize Menu
PTI Menu
Manual Check
Config Set
Optional Function
USB Menu
PTI Pass
Full PTI
Pass
Content
key in the "Initial Menu", and go to "PTI
key, then the PTI will start.
PTI Fault
Full PTI
T101 HPS cut OFF
T221 HSV malfunction
HPS cut OFF
3-5
Switch OFF
[ PTI Menu ]
PTI Menu
Full PTI
Chilled PTI
Frozen PTI
Short PTI
1/1