Daikin LX10F11B3 Service Manual page 97

Inverter container refrigeration unit, decos va
Table of Contents

Advertisement

https://daikin-p.ru
※12 Humidity Sensor Reading (Option)
1. Press
keys to select HuS-Reading and press
Then EFM runs with high speed and humidity is displayed.
When the difference between high pressure and low pressure is large (300kPa or more), unit enters
to pressure equalizing so that "Waiting---" is displayed.
Manual Check
1/3
RM ON/OFF
HuS Reading
All Sensor Calib.
---------
NEXT
※13 All Sensor Calibration (Option)
Go to All Sensor Calibration in Manual Check for SS, RS, DSS and DRS.
Manual Check
All Sensor Calibration
SS Sensor Calibration
0.1℃
RS Sensor Calibration
0.2℃
DSS Sensor Calibration
0.1℃
DRS Sensor Calibration
0.2℃
-----------
-----------
NEXT
PREV
All Sensor Calibration
OFFSET SENSOR
VALUE VALUE
SS
+0.2 ℃
+0.0 ℃
RS
+0.4 ℃
+0.0 ℃
DSS
+0.5 ℃
+0.0 ℃
DRS
+0.3 ℃
+0.0 ℃
Complete
ESC : Return
Calibration completed
Follow the same procedure for individual sensor calibration.
※14 SS Sensor Calibration (Option)
※15 RS Sensor Calibration (Option)
HuS Reading
Waiting ---
ESC : OFF and Return
All Sensor Calibration
2/3
OFFSET
VALUE
SS
+0.6 ℃
RS
+0.4 ℃
DSS
-0.7 ℃
DRS
-0.6 ℃
Enter : Delete former calibration
ESC : Return
Previous sensor values
All Sensor Calibration
OFFSET SENSOR
VALUE
SS
+0.0 ℃
RS
+0.0 ℃
DSS
+0.0 ℃
DRS
+0.0 ℃
Enter : When the temperature of
Ice-bath is stabilized at 0℃
ESC : cancel
Sensor values after the
temperature of Ice-Bath is stabilized
key to determine.
HuS Reading
--- RH
Humidity
ON
: Change
Enter : Confirm
ESC:OFF and Return
SENSOR
VALUE
+0.4 ℃
+0.7 ℃
+0.1 ℃
-0.1 ℃
VALUE
+0.2 ℃
+0.4 ℃
+0.5 ℃
+0.3 ℃
※16 DSS Sensor Calibration (Option)
※17 DRS Sensor Calibration (Option)
4-4
HuS Reading
70 %RH
Humidity
ON
: Change
Enter : Confirm
ESC:OFF and Return
All Sensor Calibration
Cancel former
calibration
Prepare
the Ice-bath
Enter : Confirm
ESC : Cancel