T081
INV
P08
check
T082
T101
EMV, ESV
P10
check
T102
T103
LSV
P12
T121
check
HSV
P14
T141
check
RSV
P16
T161
check
DMV
P18
T181
check
T201
T202
HPS
P20
T203
check
T204
Pump down
P22
T221
check
Valve leak
P24
T241
check
T501
0℃
P50
pull-down
T502
0℃
P60
No alarm No judgment
maintenance
T701
P70
Defrost test
T702
P80
-18℃ pull-down
T801
-18℃
P90
No alarm
maintenance
The frequency does not
match to command frequency.
No pressure difference
between high and low pressure.
EMV wiring failure
EMV coil burning out
EMV or ESV failure
ESV coil failure
ESV valve body failure
ESV wiring failure
ESV failure
ESV coil burning out
EMV wiring failure
EMV failure
EMV coil burning out
LSV coil failure
LSV does not operate.
LSV valve body failure
HSV coil failure
HSV does not open.
HSV valve body failure
RSV coil failure
RSV does not open.
RSV valve body failure
DMV wiring failure
DMV does not operate.
DMV coil burning out
OFF value is low.
Does not reset
①HPS failure
HPS: High pressure
②HPT failure
does not rise.
③ Gas leakage from
HPS does not operate.
HPS: High pressure
does not drop.
EEV failure
Leakage through HSV
Pump down time is
too long.
Leakage through RSV
Leakage through ESV
Leakage through HSV
Leakage through RSV
Solenoid valve
internal leakage
Leakage through ESV
Leakage through EEV
Ambient temperature
Ambient temperature is
is out of condition.
below -10℃ and above
(Unit is normal.)
43℃
Pull-down time is too long.
EOS failure
Defrost initiation
conditions out of range
HSV internal leakage
Defrost time is too long. EOS failure
Pull-down time is too long.
3-7
Check EMV coil and wiring.
Check EMV outlet pipe temperature.
Check ESV coil and wiring.
Check ESV outlet pipe temperature.
Check ESV coil and wiring.
Check clicking sound from ESV.
Check EMV coil and wiring.
Check EMV outlet pipe temperature.
Check LSV coil and wiring.
Check LSV outlet pipe temperature.
Check HSV coil and wiring
Check HSV outlet pipe temperature.
Check RSV coil and wiring.
Check RSV outlet pipe temperature.
Check DMV coil and wiring.
Check clicking sound from DMV.
①Check HPT.
② Compare to manifold
③ Remove manifold
manifold gauges
Check EEV coil, wiring, valve body.
Check HSV outlet pipe temperature.
Check RSV outlet pipe temperature.
Check ESV outlet pipe temperature.
Check HSV outlet pipe temperature.
Check RSV outlet pipe temperature.
Check ESV outlet pipe temperature.
Check EEV outlet pipe temperature.
Check ambient temperature
Check EOS.
Check HSV outlet pipe temperature.
Check EOS.
gauges.
gauges.

Hide quick links: