E707
Alarm
The power supply shut down temporarily during operation or the power supply phase waveform
Logic
was abnormal.
Possible
Power supply failure or abnormal power supply phase waveform
Causes
Trouble
Check the power supply equipment and provide the correct power supply (power supply phase
Shooting
waveform).
Unit stops once and restarts after 3 minutes standby. (Retry 9 times)
Continue operation if correct power supply is provided in that time.
Controller
In the case of a temporary power supply shut down) E707 Restart after 3 minutes of standby ×
Action
9 retries. Then, restart after 4 hours of standby.
In the case of an abnormal power supply phase waveform) E707 is generated 2 times → F703
unit stop.
026
E801
Alarm
CPU onboard battery failure (E307 and E311 are also generated.)
Logic
Possible
CPU onboard battery is drained due to salt water or moisture
Causes
Trouble
〈Permanent measures〉
Shooting
Replace CPU board (Lithium battery installed).
〈Emergency measures〉
The unit will operate. However, controller time starts from incorrect time whenever power
OFF/ON. therefore, trip data may not shown correctly.
Controller
E801 Alarm display only
Action