5.2 Protective Device and Setpoints
Component Name
High pressure switch
Pressure relief valve
Fusible plug
Built-in thermal protector
for condenser fan motor
Built-in thermal protector
for evaporator fan motor
Circuit breaker (ELCB)
Cooling Water Pressure Switch
Detector Symbol
OFF≧2400kPa(24.47kg/cm
HPS
ON≦1900kPa(19.37kg/cm
PRV
Open≧2450kPa(25.0kg/cm
95〜100℃(203〜212℉)
−
OFF≧135℃±5℃(275℉±41℉)
Q1M
ON≦86℃±15℃(187℉±59℉)
OFF≧145℃±5℃(293℉±41℉)
−
ON≦94℃±15℃(201℉±59℉)
CB
30A(100mA)
OFF≧98kPa(1.0kg/cm
WPS
ON≦39kPa(0.4kg/cm
5-3
Setting Value
2
)
2
)
2
)
2
)
2
)
Alarm
E101
F101
−
−
−
−
−
−