※18 FA Calibration (Option)
Go to FA Calibration in Manual Check first, then set ventilation volume.
Manual Check
2/3
FA Calibration
200 mm
PREV
NEXT
Step 1.
Fully open
FA intake
air hole
Ventilation
cover
FA outlet
Setting value of
ventilation volume
※19 Trip Start Time
Go to Trip Start reset by pressing
FA Calibration
Trip Start Time
Comp Running Hrs
PREV
※20 Comp. Running Hrs
1. Current Compressor Running Hrs is 1000 Hr as example below.
2. When compressor is replaced, it's recommended to reset 0 Hr by pressing
Trip Start Time
Comp Running Hrs
EFH Running Hrs
PREV
Follow the same procedure for EFH, EFL, CFH and CFL running hrs.
※21 EFH Running Hrs
※22 EFL Running Hrs
Manual Check
2/3
Step 1. Fully open Ventilation
cover
Step 2. Close ventilation
cover to zero point
Step 4 : Press ENTER
3 mm
ESC : Cancel
Step 2.
While closing the cover, adjust to the zero
position of the ventilation identification plate,
and then tighten the four wing bolts.
Wing bolt
Zero adjustment position
Sensor Information
Ventilation Volume
PREV
key for 3 seconds.
Manual Check
2/3
3mm
3 seconds
7Day12Hr
1000Hr
NEXT
Manual Check
2/3
7Day12Hr
3 seconds
1000Hr
600Hr
NEXT
Manual Check
Complete
0mm
ESC : Return
●After completing calibration,
 set ventilation volume.
①Fully open
①Fully open ventilation cover
②Move the cover down. When the ventilation volume display
 reaches the setting value, tighten the four wing bolts.
3/3
Note: If you move the cover up while configuring the
setting, perform the procedure again from step ①.
Ventilation volume is confirmed in the display
50 m3/h
according to*3 Sensor Information or battery
mode of *15 Data Information in paragraph 2.3.
Manual Check
FA Calibration
Trip Start Time
Comp Running Hrs
PREV
Manual Check
Trip Start Time
Comp Running Hrs
EFH Running Hrs
PREV
※23 CFH Running Hrs
※24 CFL Running Hrs
4-5
Manual Check
2/3
FA Calibration
PREV
FA opening 0 mm
after calibration
②Set ventilation
 volume.
2/3
3mm
0Hr
1000Hr
NEXT
key for 3 seconds.
2/3
7Day12Hr
0Hr
600Hr
NEXT
2/3
0 mm
NEXT