Daikin LX10F11B3 Service Manual page 35

Inverter container refrigeration unit, decos va
Table of Contents

Advertisement

https://daikin-p.ru
※1 Set Point temperature Change
1. Press
key to change Set Point temperature. Press
Set Temp. Range : -30.0℃ to +30.0℃ .
※2 Mode Set
Mode Set
Defrost Interval
Dehumidification Set
Bulb Mode
USDA
Automatic Setpoint Change
Automatic Cold Treatment
G-SET
Fan Speed Control
※2-1 Defrost Interval Set
1. Press
key to select defrost interval and press
Time setting: 3, 6, 9, 12, 24 Hr
Auto setting: AUTO (Defrosting will executed automatically in accordance with the state of frost
formation occurred on the evaporator coil.)
※2-2 Dehumidification Set
1. Press
or
key to select "ON" or "OFF" and press
ON : Dehumidification operation is conducted. (For unit equipped with humidity sensor)
OFF : Dehumidification operation is not conducted.
2. After selecting "ON", press
Humidity selection range: 50 to 95%RH
9Hrs
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Defrost Interval
12 Hour
▲▼ : Change
ENTER : Confirm
or
key to select the humidity setpoint and press
key to determine.
※2-1 Defrost Interval Set
※2-2 Dehumidification Set
When Reheat Coil is set to "OFF" in ※12
Configuration Set, this function will not work.
※2-3 Bulb Mode Set
※13 You cannot select this function if Bulb Mode
Function is set to "OFF" in the optional function
settings. (N/A is displayed.)
※2-4 USDA Set
※2-5 Automatic set point change
When ASC function is set to "OFF" in ※13 Optional
Function, this function will not work.
※2-6 Automatic Cold Treatment Set (Option)
When ACT function is set to "OFF" in ※13 Optional
Function and USDA is "OFF" in ※2-4 USDA
setting, this function will not work.
※2-7 G-SET Set
※2-8 Fan Speed Control
key to determine.
Defrost Interval
9 Hour
▲▼ : Change
ENTER : Confirm
key to determine.
2-6
key to determine.