102
F52E ・ F52F ・ F53B
E52D ・ E52E ・ E52F
Alarm
Logic
E52D:Fin temperature sensor failure
&
Possible
Causes
F52E:E52E is generated 4 times.
E52E:Over current failure
F52F:E52F is generated 4 times.
E52F:Compressor current sensor failure
F53B:EEPROM failure when unit is on
Trouble
Replace Inverter board
Shooting
Controller
F52E, F52F, F53B
Action
E52D
E52E, E52F
Alarm Logic
Unit stop
Restart after 3 minutes
Restart after 3 minutes (F52E, F52F is generated at 4 times retry.)
2-41
Possible Causes
Inverter board failure(Fin temperature sensor)
(Fin temperature≧150℃ or -45≦℃)
Inverter board failure(IPM part)
IPM:Intelligent Power Module
Inverter board failure(Current detection part)
Inverter board failure (EEPROM part)
EEPROM : Electrically Erasable Program ROM