Grid (Utility) Connection

5. GRID (UTILITY) CONNECTION
WARNING: To reduce the risk of injury, use the recommended
wire size above. It is very important for system safety and
efficient operation to use the appropriate wire for grid (utility)
connection.
WARNING: To prevent the risk of electric shock, make sure
the ground wire is properly earthed before operating this unit
whether the grid is connected or not.
There is an AC (Grid) circuit breaker in the distribution box. This will
ensure the inverter can be safely disconnected during maintenance and is
fully protected from overcurrent of AC input.Use the recommended wire
size below.
AC GRID
UTILITY
TYPE
GRID
GRID RATED
CONNECTION
POWER
WIRING
5 kW
REQUIREMENTS
30
USA: 240V/120V SPLIT PHASE SYSTEM
Split phase
240V/120V 60Hz
L
N
L
1
2
(Black)
(White)
(Red)
120V
120V
240Vac
NOMINAL
WIRE SIZE
VOLTAGE
240 VAC
8 AWG
PE
(Green)
PE
Torque
0.82 Nm