Commissioning
4.2 Further settings
P-No.
Note
r0755
CO: CU analog inputs actual value in percent, AI0
(terminals 3/4) [100 ≙ 100%]
p0756
CU analog input type (terminals 3, 4)
0
Unipolar voltage input (0 V ... +10 V)
1
Unipolar voltage input monitored
(+2 V... +10 V)
2
Unipolar current input (0 mA ... +20 mA)
3
Unipolar current input monitored (+4 mA ...
+20 mA)
4
Bipolar voltage input (-10 V...+10 V)
8
No sensor connected
p0757
CU analog input characteristic value x1
p0758
CU analog input characteristic value y1 [%]
p0759
CU analog input characteristic value x2
p0760
CU analog input characteristic value y2 [%]
p0761
CU analog input wire break monitoring response
threshold
p0771
CI: CU analog output signal source, AO 0
(terminals 12, 13) [100 ≙ 100%]
r0772
CU analog output, output value currently referred
r0774
CU analog output, output voltage/current actual
[100% ≙ p2001]
p0775
CU analog output activate absolute value
generation
p0776
CU analog output type
0
Current output (0 mA ... +20 mA)
1
Voltage output (0 V... +10 V)
2
Current output (+4 mA ... +20 mA)
30
P-No.
Note
p0777
CU analog output characteristic value x1 [%]
p0778
CU analog output characteristic value y1 [V]
p0779
CU analog output characteristic value x2 [%]
p0780
CU analog output characteristic value y2 [V]
p0782
BI: CU analog output invert signal source, AO 0
(terminals 12,13)
r0785
BO: CU analog outputs status word
.00
1 = AO 0 negative
p0795
CU digital inputs, simulation mode
p0796
CU digital inputs, simulation mode setpoint
p0797
CU analog inputs, simulation mode
p0798
CU analog inputs, simulation mode setpoint
p0802
Data transfer with memory card as source/target
p0803
Data transfer with device memory as
source/target
p0804
Data transfer start
12 Start transfer of the GSD for PROFIBUS
master on the memory card
p0806
BI: Inhibit master control
r0807
BO: Master control active
p0809
Copy Command Data Set CDS
p0810
BI: Command data set selection CDS bit 0
p0819
Copy drive data set DDS
p0820
BI: Drive data set selection DDS, bit 0
p0826
Motor changeover, motor number
r0835
CO/BO: Data set changeover status word
r0836
CO/BO: Command data set CDS selected
r0837
CO/BO: Drive data set DDS selected
p0840
BI: ON/OFF (OFF1)
p0844
BI: No coast down/coast down (OFF2) signal
source 1
p0845
BI: No coast down/coast down (OFF2) signal
source 2
p0848
BI: No quick stop/quick stop (OFF3) signal source
1
p0849
BI: No quick stop/quick stop (OFF3) signal source
1
p0852
BI: Enable operation
p0854
BI: Master control by PLC
p0855
BI: Unconditionally release holding brake