Motor data identification and self-optimization
If you select the MOT ID (p1900) during basic commissioning, an alarm will be issued once
the basic commissioning has been completed.
For the motor data identification, the motor must be cold. A motor in a warm operational
condition supplies unusable measurement results.
Motor data identification for dangerous loads
Secure dangerous plant and system parts before starting the motor data identification, e.g.
by fencing off the dangerous location or lowering a suspended load to the floor.
1.
2.
3.
4.
5.
6.
Now you have finished the basic commissioning and the motor identification.
SINAMICS G120C frequency converter
Getting Started, 03/2012, FW V4.5, A5E03831830B AA
Set the motor ramp-down time.
OK
Confirm that the basic commissioning has been completed:
OK
nO → YES → OK
CAUTION
The converter issues an alarm (alarm A07991).
Press the HAND/AUTO botton. The BOP-2 displays the HAND icon.
Switch on the motor.
Wait until the converter switches off the motor after the motor data
identification has been completed. This procedure takes several
seconds.
If, in addition to the motor data identification, you have also selected a
rotating measurement, the converter issues again alarm A07991.
Switch on again the motor.
Wait until the converter switches off the motor after the speed
controller has been optimized. This procedure can take up to one
minute.
Switch over from HAND to AUTO.
Commissioning
4.1 Basic commissioning with BOP-2
23