Programming
5.5 DIN_70121 parameter
preChargeCurrentInAmpere UInt
prechbrkIsUsed
shuntIsUsed
shuntValueInOhm
56
The maximum allowed charging current (in A) in the "PreCharge" phase.
If a minimum current value is required by the frequency converter to start,
its high limit is defined here.
This current must be less than or equal to the value of "maxCurrentIn-
Ampere"; otherwise the error message bit 1 (parameterization error) is set.
Bool
Monitoring the feedback of the "PreCharge breaker" and control of the
corresponding output (see section on Wiring of the frequency converter
(Page 41)).
(True = yes, False = no)
If "False" is set, the corresponding output "prechbrk" is also set perma-
nently to "False".
Bool
Monitoring the feedback of the "Shunt breaker" and control of the corre-
sponding output (see the section on Wiring of the frequency converter
(Page 41)).
(True = yes, False = no)
The "shuntValueInOhm" value must be unequal to "0"; otherwise the error
message bit 1 (parameterization error) is set.
UInt
Resistance value of shunt in Ohm (see the chapter on Protective circuit of
a converter (Page 41))