13 Troubleshooting / Fault clearance

Fault
Possible cause
No mounting kit available
No stroke
Process valve faulty
Wrong mounting kit installed
Incorrect assembly
Switch not adjusted
No feedback
Wrong mounting kit installed
Voltage is not connected
Sealing ring R inserted incorrectly
Cover H cannot
Sealing ring R damaged
be attached
Cables protruding over the edge of
the base
Grub screw K
Grub screw K unscrewed
not working
too far, nut fell out
1230
Fault clearance
Check mounting kit
Replace process valve
Replace mounting kit
Check assembly, wiring and connection
Adjust switch
Replace mounting kit
Connect voltage
Insert sealing ring R correctly
Replace sealing ring R
Check the cable routing and shorten the cables if
necessary
Reinsert the nut, screw in the grub screw K (during
assembly, only loosen the screw K, do not unscrew it)