5 Uninterruptible 24 V power supply
The procedure is as follows:
1. Select the DC UPS (1) in the hardware configuration.
2. Open the properties of the "UPS1600 xxA PN" modules (2) on slot 0.1 by
double-clicking.
3. Switch to the "Parameters" tab.
4. Set the parameters (3) as required here.
5. Compile and load the hardware configuration.
Fig. 5-4
Note
Note that remote parameterization by means of the HW configuration is only
effective if you have set the "V
"REN" position.
Integration of a SITOP 24 V Power Supply in PCS 7
Entry ID: 109481908,
V1.0,