Technical Data
11.9 Mechanical Requirements and Data
Testing
Vibration
in operation
Shock
in operation
Free fall
Tipping over
Table 11-9
Data: Mechanical requirements
11.10 Electrical-, EMC- and Climatic Requirements
11.10.1 Electrical Protection and Safety Requirements
Note:
The licenses that are currently valid for SIWAREX MS are indicated on the SIWAREX MS rating
plate.
11-60 SIWAREX MS
Standards
IEC 60068-2-6
IEC 60068-2-27
IEC 68000-2-32
IEC 68000-2-32
Test values
Test Fc
Switching cabinet installation:
0.30 mm from 10 to 57 Hz; 2 G from 57 to
150 Hz
Top-hat rail mount:
15 mm from 10 to 57 Hz; 1 G from 57 to
150 Hz
10 deflections per axis, 1 Octave/Minute
Test Ea
150 m/s
, Half sinus
2
Duration: 11 ms
Number: 3 per axis each
in neg. and pos. direction
Test Ed
Fall height 1m, 5 times in shipping
packaging
100 mm, four times without packaging