Hardware Configuration and Assembly
3. Twisted pair cables should be used for the specified lines and should also be
shielded:
-
Sensor line SEN+ and SEN-
-
Measuring voltage lines SIG+ and SIG-
-
Supply voltage lines EXT+ and EXT-
We recommend using the cable indicated in chapter 10 Accessories.
4. The shielding must be connected to the shielding connection clamp.
The maximum distance between the SIWAREX MS and the load cell is applicable
when using the recommended cables.
The power supply (6V) for the load cells comes from the SIWAREX MS. (terminal
EXC+ and EXC-).
The connection should be made using the cable indicated in chapter
10 Accessories.
Connection and signal designations
Table 4-2
Load cell connections
4-14
SIWAREX MS
SEN+
SEN-
SIG+
SIG-
EXC+
EXC-
Comment
Sensor line +
Sensor line -
Measurement line +
Measurement line -
Load cell supply output +
Load cell supply output -