Boiler/group "2"

Select "Boiler" for weather-compensated control units
(see page 63).
Coding
Coding in the delivered condition
01:1
Single boiler system (only for con-
stant temperature control units)
04:1
Minimum burner pause time sub-
ject to the boiler load (specified by
coding card)
06:...
Maximum limit of boiler water tem-
perature, specified in °C by coding
card
07:1
Boiler number in multi boiler sys-
tems (only for constant tempera-
ture control units)
08:...
Maximum burner heating output in
kW, in multi boiler systems
0d:0
Never adjust
0E:0
Never adjust
13:1
Never adjust
14:1
Never adjust
15:1
Never adjust
21:0
No service interval set (in hours
run)
23:0
No time set for burner service in-
terval
24:0
"Service" not shown on the dis-
play
28:0
No burner interval ignition
2E:0
Never adjust
2F:0
Venting program/filling program
disabled
30:3
Boiler circuit pump speed-control-
led via 0-10 V interface
Select "2" for constant temperature control units (see
page 63).
Possible change
01:2
Multi boiler system with Vitotronic
300-K
04:0
Minimum burner pause time set per-
manently (specified by coding card)
06:20
Maximum limit of boiler water tem-
to
perature within the ranges specified
06:127
by the boiler
07:2
Boiler number 2 to 8 in multi boiler
to
systems
07:8
08:0
Maximum burner heating output ad-
to
justable in 1 kW increments, from 0
08:199
to 199 kW (limited by boiler-specific
parameters)
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10,000 h
One step
23:1
Interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" shown on the display
(address is set automatically and
must be reset manually after a serv-
ice).
28:1
Time interval adjustable from 1 h to
to
24 h. The burner is force-started for
28:24
30 s at a time (only when operating
with LPG).
2F:1
Venting program enabled
2F:2
Filling program enabled
30:0
Connection of multi-stage boiler
circuit pump
Operation with low loss header
(single or multi boiler system)
30:1
Boiler circuit pump speed-controlled
30:2
Boiler circuit pump speed-controlled
with flow rate
Code 2
100 h
69