Code 2
Solar/group "4"
(cont.)
Coding in the delivered condition
04:4
Controller amplification of speed
control 4 %/K
05:10
Min. speed of the solar circuit
pump 10 % of max. speed
06:75
Max. speed of the solar circuit
pump 75 % of max. possible speed
07:0
Interval function of solar circuit
pump switched off
08:60
Set DHW temperature (maximum
cylinder temperature) 60 °C
09:130
Maximum collector temperature (to
protect system components)
130 °C
0A:5
Temperature differential for stagna-
tion time reduction 5 K
Reduction in the speed of the solar
circuit pump to protect system
components and heat transfer me-
dium.
0b:0
Frost protection function for solar
circuit switched off
0C:1
Delta-T monitoring ON
No flow rate captured in the solar
circuit, or flow rate too low.
0d:1
Night-time DHW circulation moni-
toring switched on.
Unintentional flow in the solar cir-
cuit is captured (e.g. at night).
0E:1
Heat statement in conjunction with
Viessmann heat transfer medium.
0F:70
Solar circuit flow rate at maximum
pump speed 7 l/min
10:0
Target temperature control switch-
ed off (see coding address "11").
11:50
Set solar DHW temperature 50 °C
72
Possible change
04:1
Controller amplification adjustable
to
from 1 to 10 %/K
04:10
05:2
Min. speed of solar circuit pump is
to
adjustable from 2 to 100 %
05:100
06:1
Max. speed of solar circuit pump is
to
adjustable from 1 to 100 %
06:100
07:1
Interval function of solar circuit pump
switched on
To capture the collector temperature
more accurately, the solar circuit
pump periodically starts for a short
duration.
08:10
Set DHW temperature adjustable
to
from 10 to 90 °C
08:90
09:20
Temperature adjustable from 20 to
to
200 °C
09:200
0A:0
Stagnation time reduction not active
0A:1
Temperature differential adjustable
to
from 1 to 40 K
0A:40
0b:1
Frost protection function for solar cir-
cuit switched on (not required with
Viessmann heat transfer medium)
0C:0
Delta T monitoring switched off.
0d:0
Night-time DHW circulation monitor-
ing OFF
0E:2
Never adjust
0E:0
No heat statement
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min
0F:255
1 step
10:1
Target temperature control switched
on.
11:10
The set solar DHW temperature is
to
adjustable from 10 to 90 °C
11:90
0.1 l/min