Viessmann VITODENS 200-W B2HA Installation And Service Instructions Manual page 88

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 200-W B2HA:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code
Const.
displayed
30
X
38
X
40
44
48
4C
50
X
58
X
90
X
91
X
92
X
93
X
94
X
98
X
99
X
9A
X
88
Weather-
System characteris-
comp.
tics
X
Burner blocked
X
Burner blocked
X
Mixer being closed
X
Mixer being closed
X
Mixer being closed
X
Mixer being closed
X
No DHW heating by
the boiler
X
No DHW heating
X
Control mode
X
Control mode
X
No solar DHW heat-
ing
X
Control mode
X
No solar DHW heat-
ing
X
Control mode
X
Control mode
X
No solar DHW heat-
ing
Cause
Measures
Short circuit, boiler
Check boiler water tem-
water temperature
perature sensors (see
sensor
page 96)
Lead break, boiler
Check boiler water tem-
water temperature
perature sensors (see
sensor
page 96)
Short circuit, flow
Check flow temperature
temperature sen-
sensor (see page 98)
sor, heating circuit
2 (with mixer)
Short circuit, flow
Check flow temperature
temperature sen-
sensor (see page 98)
sor, heating circuit
3 (with mixer)
Lead break, flow
Check flow temperature
temperature sen-
sensor (see page 98)
sor, heating circuit
2 (with mixer)
Lead break, flow
Check flow temperature
temperature sen-
sensor (see page 98)
sor, heating circuit
3 (with mixer)
Short circuit, cylin-
Check cylinder tempera-
der temperature
ture sensor (see
sensor
page 96)
No DHW heating
Check cylinder tempera-
by the boiler
ture sensor (see
page 96)
Short circuit, tem-
Check sensor
perature sensor
control module.
/
Short circuit, tem-
Check sensor
perature sensor
control module.
Short circuit, col-
Check temperature sen-
lector temperature
sor
&
sensor
module or sensor on the
Vitosolic.
Short circuit, cylin-
Check temperature sen-
der temperature
sor at terminal S3 on the
sensor
Vitosolic.
Short circuit, cylin-
Check temperature sen-
der temperature
sor
%
sensor
module or sensor on the
Vitosolic.
Lead break, tem-
Check sensor
perature sensor
control module.
/
Lead break, tem-
Check sensor
perature sensor
control module.
Lead break, collec-
Check temperature sen-
tor temperature
sor
&
sensor
module or sensor on the
Vitosolic.
/
on solar
on solar
on solar control
on solar control
/
on solar
on solar
on solar control

Advertisement

Table of Contents
loading

Table of Contents