Viessmann VITODENS 200-W B2HA Installation And Service Instructions Manual page 77

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 200-W B2HA:
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for weather-
compensated control units)
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
d3:14
Heating curve slope = 1.4
d4:0
Heating curve level = 0
d5:0
The external operating program
changeover switches the operating
program to "Constant operation
with reduced room temperature" or
"Standby mode" (only for weather-
compensated control units)
d6:0
Heating circuit pump remains in
control mode at "External blocking"
signal
d7:0
Heating circuit pump remains in
control mode at "External demand"
signal
d8:0
No operating program changeover
via EA1 extension
RT
+ 5 K
>
actual
set
RT
+ 4 K
>
actual
set
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
- 1 K
>
actual
set
RT
- 2 K
>
actual
set
(cont.)
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d3:2
The heating curve slope is adjusta-
to
ble from 0.2 to 3.5 (see page 48)
d3:35
d4:–13
The heating curve level is adjustable
to
from
d4:40
d5:1
The external operating program
changeover switches to "Constant
operation with standard room tem-
perature" (subject to coding ad-
dresses 3A, 3b and 3C)
d6:1
At signal "External blocking" the
heating circuit pump is stopped
(subject to coding addresses 3A, 3b
and 3C)
d6:2
At signal "External blocking" the
heating circuit pump is started (sub-
ject to coding addresses 3A, 3b and
3C)
d7:1
At signal "External demand" the
heating circuit pump is stopped
(subject to coding addresses 3A, 3b
and 3C)
d7:2
At signal "External demand" the
heating circuit pump is started (sub-
ject to coding addresses 3A, 3b and
3C)
d8:1
Operating program changeover via
input DE1 at EA1 extension
d8:2
Operating program changeover via
input DE2 at EA1 extension
d8:3
Operating program changeover via
input DE3 at EA1 extension
Code 2
+ 4 K
+ 3 K
+ 2 K
+ 1 K
- 1 K
- 2 K
- 3 K
13 to 40 (see page 48)
77