Viessmann VITODENS 200-W B2HA Installation And Service Instructions Manual page 60

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 200-W B2HA:
Table of Contents

Advertisement

Code 1
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Extended economy function mixer
A7:0
Without mixer economy function
Only for a weather-compensated
control unit and heating circuit with
mixer.
Pump idle time, transition reduced mode
A9:7
With pump idle time: heating circuit
pump "OFF" if the set value is al-
tered through a change in operat-
ing mode or through a change in
the set room temperature (only for
weather-compensated control
units)
Weather-compensated/room temperature hook-up
b0:0
With remote control: heating mode/
reduced mode: weather-compen-
sated (only for weather-compensa-
ted control units). Change code
only for the heating circuit with
mixer.
Economy function room temperature
b5:0
With remote control: no room tem-
perature-dependent heating circuit
pump logic function (only for
weather-compensated control
units). Change code only for the
heating circuit with mixer.
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
60
RT
+ 5 K
>
actual
set
RT
+ 4 K
>
actual
set
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
- 1 K
>
actual
set
RT
- 2 K
>
actual
set
(cont.)
Possible change
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been trying to
close for longer than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function
If there is a risk of frost
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15. The higher the value, the
A9:15
longer the pump idle time.
b0:1
Heating mode: weather-compensa-
ted
Reduced mode: with room tempera-
ture hook-up
b0:2
Heating mode: with room tempera-
ture hook-up
Reduced mode: weather-compensa-
ted
b0:3
Heating mode/reduced mode: with
room temperature hook-up
b5:1
For heating circuit pump logic func-
to
tion, see the following table:
b5:8
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
+ 4 K
+ 3 K
+ 2 K
+ 1 K
- 1 K
- 2 K
- 3 K