5. OPERATING PROCEDURES
_.I
MELSEC-A
5.5
Functbns of
the
ABPUE
on a
YELSECNET(/B)
Data
Link
System
The A8PUE can execute testing, reading, writing, and monitoring of programs
for the PC CPU of another station connected to the MELSECNET(/B) data link
system (hereafter called MELSECNET).
(I) Stations that
can access another station on MELSECNET are in the
following ranges:
When the A8PUE is connected to a master station
The self and all local stations can be accessed.
Remote I/O stations cannot be accessed.
Set and perform monitoring and testing for the I/O module of a remote
I/O station at the self {master station).
When the A8PUE is connected to a local station
The self and master stations can be accessed. Other local stations
and remote I/O stations cannot be accessed.
When the A8PUE is connected to a remote I/O station
The self and master stations can be accessed. Other local stations
and remote other I/O stations cannot be accessed.
(2) Functions when accessing another station on MELSECNET
When connecting the A8PUE to a master station/local station and
accessing the self
It
is possible to operate all functions.
When connecting A8PUE to a remote I/O station and accessing the
self
Link monitoring (see Section
6.9.4) and PC number setting (see
Section 6.9.10) are possible.
When connecting the A8PUE to a master station
and accessing a
local station
It is possible to operate functions that are the
same as when the
A8PUE was connected to the self
-
except for link monitoring (see
Section 6.9.4) and PC memory all clear (see Section 6.9.7).
When connecting the A8PUE to a local station and accessing a
master station
It
is possible to operate functions that are the
same as when the
A8PUE was connected to the self
-
except for link monitoring (see
Section 6.9.4) and PC memory all clear (see Section 6.9.7).
When connecting the A8PUE to a remote I/O station and accessing
a master station
It is possible to operate functions that are the
same as when the
A8PUE was connected to the self
-
except for link monitoring (see
Section 6.9.4) and PC memory all clear (see Section 6.9.7).