Baxi Ecogen 24/1.0 Installation & Servicing Instructions Manual page 77

Gas fired wall mounted condensing boiler and power generator
Table of Contents

Advertisement

thermo
127: Legionella
Legionella temperature not achieved within 48 hours
temperature
157: Boiler
Boiler flow overheat thermostat / safety chain open
Flow
Thermostat
158:
Condensate switch of safety chain opened
Condensate
164: Flow
Low flow or air in system / faulty connection or water flow sensor
press switch
HC
253:
The controller is unable to identify the error cause
Ambiguous err
cause
257: Pack
Fault pack temp sensor
sensor
258: Pack
Internal ambient temperature to high
overtemp
259: CJC
Fault cold junction compensation sensor
sensor
261: Loss of
No flame after five ignition tries in Engine
flame Eng bu
262: Loss of fl'
No flame after five ignition tries in Supplementary
Supp bu
263: Engi bu
Multiple communication request of Engine Burner Control Unit unsuccessful.
BCU failure
1) Failure caused by BCU
2) BCU Communication Timeout on Main Control Board
264: Supp bu
Multiple communication request of Supp. Burner Control Unit unsuccessful.
BCU failure
1) Failure caused by BCU
2) BCU Communication Timeout on Main Control Board
265: BCU
Not supported in Main Control Board
failure
266: Fan fault
Fan fault: The fan speed differs from its set point for more than 30 seconds.
267: Fan
Fan calibration error: After power­up the test threshold of 4,700 rpm was not attained.
calibration
268: Spool
Feedback signal of spool valve did not reach required value within detection time ­
valve fault
typically 60 sec.
269: Spool
During start up the feedback signal of the spool valve did not register a correct
valve calib
calibration
page 78
 
Error code:
Description
Display
270: exc temp.
Excessive max temperature difference across the heat exchanger during 5 minutes or
diff h'exch
excessive limit temperature difference. If temperature difference fell below (threshold ­
switching differential boiler): automatic reset
­ when the maximum setting was exceeded immediately
­ when the limit value was exceeded after 10 minutes
274: Dry fire
Flow sensor did not detect at least 4 L/min within 4 mins
prot
278: Max Temp
Maximum flow temperature rise exceeded, automatic reset after 10 minutes
Rise
280 : Inner iron
Engine dome overtemp has operated
overtemp
281: Dyn
Dynamic absorber over­travel switches have been activated
absorber overtr
282:
G83/ENS module has detected an unhealthy mains condition
G83/ENS/G1M
283: Altern'
Alternator overload protection thermostat has operated
overload
284: WCS over
Water cooled seal thermostat has operated
temp
285: Alternat SC Power monitor IC has detected a short­circuit condition
286: Eng head
Engine head temperature thermocouple measurement has exceeded 565 degrees C
over temp
287: Eng head
Engine head temperature thermocouple measurement below 103 degrees C when the
under temp
CX relay is energised
288­297:
Milligrid and water cooled thermostat continuity problems
Various fault
messages
298: False
Ionisation probe of engine burner detected false flame
flame engine
burner
299: False
Ionisation probe of supplementary burner detected false flame
flame
supplementary
burner
300: Eng head
Engine head control temperature less than 150 degrees C when connected to the grid
undert SW
 
 
C
UR
UR
C
UR
UR
D
AR
AR
I
UR/SR UR/SR
F
 
 
C
AR
AR
C
AR
 
C
UR
 
E
 
UR
E
F
ARP
AR
 
F
ARP
 
AR
 
 
F
SR
SR
G
ARP
ARP
G
SR
SR
H
SR
SR
H
Lockout/reset
Fault
action
Section
Eng
Sup
I
AR
AR
AR
AR 10'
UR
UR
I
 
AR 10'
I
AR
 
P
SR
 
P
AR
 
P
SR
 
P
SR
SR
J
AR
 
P
SR
 
K
AR
 
N
SR
 
K / O
AR
 
 
 
AR
 
UR
 
N