To prevent reading from the panel:
1. From the Main Menu, choose Activate.
2. Choose Remote Read Lock.
3. Choose By Panel, and then enter the panel address (PP).
— or —
Choose All Panels.
4. Enter the access level password.
To allow reading from the panel:
1. From the Main Menu, choose Restore.
2. Choose Remote Read Lock.
3. Choose By panel, and then enter the panel address (PP).
— or —
Choose All Panels.
4. Enter the access level password.

Testing a carbon monoxide (CO) detector

V-Series carbon monoxide (CO) detectors have an accelerated response mode
that you can use when testing. In normal mode, V-Series CO detectors activate
after carbon monoxide levels reach 400 ppm (parts per million) for 4 minutes.
In accelerated response mode, V-Series CO detectors activate within 4 to
8 seconds after reaching 400 ppm.
Notes
The V-Series CO detector normal response rate mimics the normal
absorption rate of CO in the bloodstream.
If you do not restore the response mode, CO detection returns to its normal
response time after 4 hours.
To change the CO rate of detection:
1. From the Main Menu, choose Activate.
VM-1 User Guide
Chapter 3: Advanced operating instructions
37