3. Choose Display and scroll through the report.
— or —
Choose Print Locally.
4. When finished, press the Backspace button to return to the Reports Menu or
press the Menus button to exit.

Silencing the panel buzzer

The VM-1 control panel sounds the panel buzzer when an event message is
posted into one of the event message queues. Pressing the Ack/Panel Silence
button or acknowledging the event message silences the buzzer. The panel
buzzer automatically re-sounds when a new event message is posted or when
the panel trouble re-sound timer expires (typically after 24 hours).
Notes
The panel buzzer may be configured to sound periodically to remind that the
panel has been silenced.
For nonlatching events, the panel buzzer automatically silences when the
event is restored.
Pressing the Panel Silence button also silences the buzzer on remote
annunciators, provided that the remote annunciators are communicating.
To silence the panel buzzer:
1. Press the Ack/Panel Silence button or acknowledge the event message.

Silencing alarm signals

WARNING:
Risk of death or serious injury. The protected premises may be
occupied. Do not silence alarm signals or reset the control panel unless you are
authorized to do so and only after all occupants have been evacuated.
Pressing the Alarm Silence button silences all audible alarm signals and, if
configured, all visible alarm signals.
Depending on the system configuration, the alarm silence operation:
May be inhibited for 1 to 3 minutes after an alarm event
VM-1 User Guide
Chapter 2: Basic operating instructions
27