Siemens SINAMICS S120 Equipment Manual page 61

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
Use of thermally insulating mats
In the electrical cabinet design shown as example, thermally insulating mats must be used in
order to maintain the following boundary conditions:
• The thermally insulating mats ensure that the power loss specified in the technical data is
dissipated to the coolant, and the specified power loss to the environment is not
exceeded.
• The lateral thermally insulating mats (
becoming too hot.
• The thermally insulating mat between the filter reactor and filter module (
filter module from overheating as a result of the power loss in the filter reactor.
Risk of fire due to ground fault/short-circuit
Inadequate installation of the cables between the filter reactor and the filter module can
result in a ground fault/short-circuit and place persons at risk as a result of the associated
smoke and fire.
• Apply the local installation regulations to avoid this fault.
• Protect the cables against mechanical damage.
• Also implement one of the following measures:
Installation kit for Active Interface Module in Rittal TS8
An installation kit for installing an Active Interface Module in a Rittal TS8 electrical cabinet
can be ordered under Article No. 6SL3065-1FJ00-0AA0.
The installation kit includes the following components:
● Support plate for the filter reactor
● Holding plates for the lateral insulating mats
● Insulating mat between the filter reactor and the filter module
● Insulating mats
● Support bracket
● Insulation materials (screws, nuts)
● Installation instructions
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
) prevent the adjacent cabinets and/or doors from