Siemens SINAMICS S120 Equipment Manual page 265

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Material
Gaskets
Hose connections
Note
Checking the hose lines
The inspection intervals depend on the prevailing ambient conditions.
The following points should be noted for the coolant hoses:
• Damage through abrasion points
• Embrittlement (e.g. forming of cracks)
• Leaks
• The hose slipping out of the coupling
• Deformations that do not comply with the natural shape of the hose (e.g. separation of
layers and blistering)
• Exceeding the storage and use times
In accordance with the accepted rules and standards, we recommend a testing cycle of
five years with the appropriate test pressure (twice the operating pressure).
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Cooling circuit, coolant properties and protection against condensation
Used as
Pipes, valves and
Use of Viton, AFM34, EPDM, NBR is recommended.
fittings
Pipe-hose transition
Secure with clips conforming to DIN2817, available, e.g. from the
Telle company .
Hose connectors manufactured out of a copper-nickel alloy are
included in the accessories pack for devices with copper-nickel
heat exchanger Installing the hose connectors using security
clamp collars (Page 273).
Used with SINAMICS S120 water cooled
9.3 Materials