Siemens SINAMICS S120 Equipment Manual page 166

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules
6.6 Technical specifications
Table 6- 15
Technical data for Motor Modules, DC 675 ... 1035 V (line voltage 3 AC 500 ... 690 V), Part 3
Article number
Type rating
- Based on I
(50 Hz 690 V)
L
- Based on I
(50 Hz 690 V)
H
- Based on I
(50 Hz 500 V)
L
- Based on I
(50 Hz 500 V)
H
- Based on I
(60 Hz 575 V)
L
- Based on I
(60 Hz 575 V)
H
Output current
- Rated current I
N A
- Base load current I
L
- Base load current I
H
- Max. output current I
max A
DC link current
- Rated current I
when fed via
N DC
- Basic Line Module
- Active Line Module
- Base load current I
when fed via
L DC
- Basic Line Module
- Active Line Module
- Base load current I
H DC
- Basic Line Module
- Active Line Module
Supply voltages
- Electronics power supply
- DC link voltage
- Output voltage
DC link capacitance
Rated pulse frequency
- Max. pulse frequency without derating
- Max. pulse frequency with derating
Electronics current consumption (24 V DC)
Cooling method
Power loss, max.
3)
- At 50 Hz 690 V
- At 60 Hz 575 V
- Dissipated to the ambient air
Max. coolant temperature
- without derating
- with derating
Rated flow rate
Pressure drop, typical
at the rated flow rate
4)
Liquid volume of integrated heat exchanger
Sound pressure level
L
(1 m) at 50/60 Hz
pA
166
6SL3325–
kW
1)
kW
1)
kW
1)
kW
1)
HP
2)
HP
2)
A
A
A
A
A
A
A
A
when fed via
A
A
V
DC
V
DC
V
ACrms
μF
kHz
kHz
kHz
A
kW
kW
kW
°C
°C
l/min
Pa
dm³
dB(A)
1TG41–3AA7
1TG41-6AA7
7)
7)
1200
1500
1000
1260
900
1000
800
900
1250
1500
1000
1250
1270
1560
1230
1500
1136
1284
1600
1950
1550
1903
1395
1714
1500
1800
1353
1650
1384
1680
1250
1550
24 (20.4 ... 28.8)
675 ... 1035
0 to 0.72 x DC link voltage
19330
21000
1.25
1.25
1.25
1.25
7.5
7.5
1.46
1.46
Water cooling system with integrated heat exchanger manu-
factured out of a copper-nickel alloy
13.49
17.9
11.84
15.7
0.57
0.78
45
45
50
50
27
27
70000
70000
1.56
1.56
56
56
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0